Toshiba 480 V Power Supply User Manual


 
39
G8000 Series Installation and Operation Manual
11.3 UPS Power Cable Conduit Landing Plates
Cable conduit landing plates are provided at the bottom of the 80 kVA and100 kVA UPS, at the top and
bottom of the 150/225 kVA UPS (Older models of the G8000 150/225 kVA UPS do not come equipped with
an upper conduit landing plate.), and at the top only of the 300/500kVA. The recommended conduit landing
arrangements are illustrated in Figure 11.9 thru 11.13.
The ve (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening
behind the conduit landing plates.
BASE PLATES - DIMENSIONS
0.78 in.
0.78 in.
23.74 in.
4.74 in.
CONTROL
WIRES
AC
INPUT
BYPASS
AC OUT-
PUT
BATTERY
Recommended
Conduit Placement
Order in Top Conduit
Landing Plate
21.85 in.
3.37 in.
7.48 in.
5.9 in.
23.11 in.
5.9 in.
23.73 in.
UPS BASE
BOTTOM ENTRY DIMENSIONS
FRONT OF UPS
FIGURE 11.9 - BOTTOM CONDUIT LANDING PLATES FOR 80/100/125 KVA