Toshiba 480 V Power Supply User Manual


 
51
G8000 Series Installation and Operation Manual
G8000 Specications
Model Number
T80S3K08
KK6XSxx
T80S3K10
KK6XSxx
T80S3K12
KK6XSxx
T80S3K15
KK6Xxx
T80S3K22
KK6XSxx
T80S3K30
KK6XSxx
T80S3K50
KK6XSxx
Environ-
ment
(cont.)
Dimension - Width 36.8 in. (935 mm) 55.1 in. (1400 mm) 76.8 in.
1951 mm)
101.8 in.
(2586 mm)
Depth 32.5 in. (826 mm) 31.8 in. (808 mm) 35.7 in.
(907 mm)
37.4 in.
(945 mm)
Height 79.2 in. (2012 mm) 79.4 in.
(2017 mm)
79.7 in.
(2024 mm)
Cable Access Bottom Access Top or Bottom Access Top Access
Minimum
Clearance
Top: 15.75” (400 mm)
Front: 43 7/16” (1100 mm) 37 in.
(940 mm)
Back/Left/Right Sides: Zero
Enclosure NEMA 1
Heat Loss to be
Removed @ Full
Load
28,321
BTUs/hr
33,746
BTUs/hr
37,281
BTUs/hr
38,524
BTUs/hr
67,667
BTUs/hr
89,011
BTUs/hr
110,262
BTUs/hr
Audible Noise 65 dBA @ 1m Typical 68 dBA @ 1m Typical 72 dBA @
1m Typical
78 dBA @
1m Typical
Operating Tem-
perature
32˚F to 86˚F (0˚C to 30˚C) for 1.0PF 32˚F to 104˚F (0˚C to 40˚C) for 0.8 PF
Operating Humid-
ity
30% to 90% Non-Condensing
Operating Altitude 3200 ft. (1000 m)
Listings/Standards UL 1778; UL 17025, cUL 22.2, No. 107.1; ANSI C62.41 (IEEE 587 Cat B) NFPA 70; OSHA; ISO
9001; IEC298 IP20
Monitor-
ing
Warranty 3 Years Parts and Labor
Dry Contacts
Included
Yes, for input and output signals
RS232 Port Included
Intelligent Monitor-
ing (Optional)
SNMP; Modbus RTU; Modbus TCP; BACNET, METASYS
Display LCD Touch Panel for Local Monitoring, Operation and control
EPO
Emergency Power
Off
Included
Cong-
uration
Input Conv. 6-diode Bridge Rectier
Battery Cct IGBT Chopper
Out. Inv. IGBT Converter with PWM