Toshiba DEV001Z Network Hardware User Manual


 
E6581268
- 15 -
3.4.5.3. Instance 100/150 – Toshiba Specific (f894 = 2)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 DC braking
ACC1/
ACC2
PI off THR2
Preset
Speed4
Preset
Speed3
Preset
Speed2
Preset
Speed1
1
Command
link
*
Frequency
link
*
Reset trip
Emergency
stop
Free run (ST) Run/stop
Fw/
Reverse
Jog
2 Drive Reference Speed Hz (Low byte) **
3 Drive Reference Speed Hz (High byte) **
Fig. 5 Output Instance 100 Layout
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 DC braking ACC2 PI
tHr2
(VF2+tH2)
-
ALARM
(fc91)
EMG FL
1-
READY
without
ST/RUN
READY
with ST/ RUN
Emergency
stop
Free run
(ST)
Run/
Stop
Fw/
Reverse
Jog
2 Drive Actual Speed Hz (Low byte)
3 Drive Actual Speed Hz (High byte)
Fig. 6 Input Instance 150 Layout
* Bit 14 and 15 of the instance 100 byte 0 are defined as follows.
Bit 15 (Command link)......... When “0” is set, the other command does not work except bit 12 and 13,
Run/Stop is according to setup of the parameter cmod.
Bit 14 (Frequency link)......... When “1” is set, bytes 2 and 3 are enabled. When “0” is set, Drive Reference
Speed is according to setup of the parameter fmod.
**
Drive Reference Speed is set up by 0.01Hz unit and the hexadecimal number.
For example, when "Frequency reference" is set up to 60Hz, since the minimum unit is 0.01Hz,
60 / 0.01 = 6000 = 0x1770 (Hex.)