Toshiba DEV001Z Network Hardware User Manual


 
E6581268
- 4 -
2. Connection Information
2.1. Connection Sizes
Connection Instance Produced Consumed
I/O Messaging 4 or 8 bytes 4 or 8 bytes
Explicit Messaging 49 bytes 49 bytes
Notes
- For the Explicit Messaging connection, this is the maximum message length: shorter messages are also acceptable.
- For the Polled I/O connection, if the actual consumed data size is less than the connection instance’s
consumed_connection_size attribute, the consumed data will be ignored, but the connection will otherwise produce
normally. If the actual consumed data size is larger than the connection instance’s consumed_connection_size attribute,
the consumed data will be ignored and the connection will not produce.
2.2. Names and functions
The external view of this option and the name of each part are shown below:
SW1: Terminal F, R
SINK/SOURCE switching
MS (Module status) LED
(Refer to 2.3)
Common serial communication connector DeviceNet connector
NS (Network status) LED
(Refer to 2.3)
SW2: Factory set up
* Please do not change this switch from the factory
shipments. It becomes the cause of failure.
F R VIA CC P24
G/E FLA FLB FLC
RJ45