Toshiba G8000 Power Supply User Manual


 
34
G8000 Series Installation and Operation Manual
The terminal busses for the 300 kVA UPS are located inside at the top of the unit. See Figure 11.6. The
dashed line indicates the side view of the bolt holes. Use 1/2 inch bolts to attach the lugs.
See Tables 11.5 for recommended cable size for the 300 kVA UPS. See Table 11.4 and Table 11.6 for
vendor recommended lugs.
FIGURE 11.7 - TERMINAL BUSSES OF THE 300 KVA UPS
Figure 11.7 shows the four (4) cable knockout plates provided at the top of the 300 kVA UPS. Seven (7)
holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the
knockout plates.
FIGURE 11.8 - CABLE KNOCKOUT PLATES (300 KVA
G8000 Series Installation Manual
30
CONTROL
WIRES
0.8”
0.8”
2” Dia.
3” Dia.
AC INPUT
BYPASS
A
C OUTPUT
BATTERY
Plate #2
Plate #1
1 2 3 64 5 7 8 9 10 11 12
AC INPUT
3-phase 3-wire
BYPASS INPUT
3-phase 4-wire
BATTERY
AC OUTPUT
3-
p
hase 4-wire
U V W
- +
U V WVUNW
The cable knockout plates are provided at the bottom of each 100/150/225kVA UPS. The recommended
hole locations are illustrated in Figure 11.3 and 11.4.
The five (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening
behind the knockout plates.
FIGURE 11.3 - CABLE KNOCKOUT PLATES100kVA (T80S3K10KK6XS2H
)
FIGURE 11.4 - CABLE KNOCKOUT PLATES
100kVA (T80S3K10KK6XSNH
); 150/225kVA
The terminal busses are located inside at the top of the 300kVA UPS. See Figure 11.5. The dashed line
indicates the side view of the bolt holes. Use 1/2 inch bolts to attach the lugs.
See Table 11.6 for recommended cable size and tightening torque for the 300kVA UPS. See Table 11.7
for vendor recommended lugs.
FIGURE 11.5 - TERMINAL BUSSES OF THE 300kVA UPS
0.4”
0.8”
4
Dia
.
2” Dia.
AC INPUT
BYPASS
AC OUTPUT
BATTERY
CONTROL
WIRES
Plate #1
Plate #2
Plate #3
-
G8000 Series Installation Manual
32
Figure 11.6 shows the four (4) cable knockout plates provided at the top of the 300kVA UPS. Six (7)
holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the
knockout plates.
FIGURE 11.6 - CABLE KNOCKOUT PLATES (300kVA)
0.8”
0.4”
4” Dia.
0.6”
1.5”
2“ Dia.
0.6”
2“ Dia.
Pl
ate #
2 Plate #3
Plate #1
Plate #4
GROUND WIRE
AC INPUT
BYPASS
AC OUTPUT
CONTROL WIRES
BATTERY
-
+
PLATE #3PLATE #2
PLATE #4
PLATE #1
-
+