Toshiba G8000 Power Supply User Manual


 
35
G8000 Series Installation and Operation Manual
TABLE 11.5 RECOMMENDED CABLE SIZE AND TIGHTENING TORQUE FOR 300 KVA UPS
Bus Number Cable Size Tightening Torque
1 Two 4/0 AWG or larger 275 in-lbs (3.2 kg-m)
2 Two 4/0 AWG or larger 275 in-lbs (3.2 kg-m)
3 Two 4/0 AWG or larger 275 in-lbs (3.2 kg-m)
*4 Three 350 MCM or larger 275 in-lbs (3.2 kg-m)
*5 Three 350 MCM or larger 275 in-lbs (3.2 kg-m)
6 Two 4/0 AWG or larger 275 in-lbs (3.2 kg-m) )
7 Two 4/0 AWG or larger 275 in-lbs (3.2 kg-m)
8 Two 4/0 AWG or larger 275 in-lbs (3.2 kg-m)
9 Two 4/0 AWG or larger 275 in-lbs (3.2 kg-m) )
10 Two 4/0 AWG or larger 275 in-lbs (3.2 kg-m)
11 Two 4/0 AWG or larger 275 in-lbs (3.2 kg-m)
12 Two 4/0 AWG or larger 275 in-lbs (3.2 kg-m)
NOTE: MAXIMUM CABLE SIZE IS 600MCM
*TWO BATTERY STRINGS OR MORE (CONSULT FACTORY IF USING ONE
BATTERY STRING)
TABLE 11.6 RECOMMENDED LUGS FOR USE WITH 300 KVA UPS
Terminal Bus # Recommendation
Vendor Catalog #
1
ILSCO
TA-600
AU-600
2
3
4
ILSCO
TA-600
T3A2-600N
5
6
ILSCO
TA-600
AU-600
7
8
9 TA-600, T3A2-600N
10
TA-600
AU-600
11
12