43
G8000 Series Installation and Operation Manual
12 UPS Specications
12.1 General Specication
Terms Specication Remarks
Conforming Standard UL1778-2001 UL, cUL
Ambient Temperature 32 – 104 °F (0 – 40 ° C)
Relative Humidity 30% – 90% Non-condensing
Altitude
< 3,280 ft (< 1,000 m) Contact Toshiba Technical Support for
instalation above 3280 ft. (1000 m)
Audible Noise 68 dB(150/225 kVA), 72 dB(300 kVA) 1m (39”) away from front
Insulation Resistance 3 MΩ With 500V-Megger
Insulation Breakdown
AC 2 kV – 1 min. Main Circuit
AC 1.5 kV – 1 min. External Interface
AC 500 V – 1 min. Control Circuit
12.2 Mechanical Specication
Rated Capacity
100 kVA:
T80S3K10KK6XS2H
100 kVA:
T80S3K10KK6XSNH
Cabinet
Protection
Conformity
IEC298 IP20*
Exterior Paint Sherwin Williams, HHT2-7055, 079 Beige Texture
Panel Thickness
FRONT: 1.6 mm (1/16 in.)
BACK/SIDE/TOP: 1.2mm (3/64 in.)
BOTTOM: 3.2mm (1/8 in.)
Input/Output
Cabling Entrance
BOTTOM
Ground/Control
Wiring Entrance
BOTTOM
Outline
Dimension
W: 36.8 in. (935 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2,012 mm)
W: 55.1 in. (1,400 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2,012 mm)
Unit Weight 1,800 lbs (816 kg) 2,500 lbs (1,134 kg)
Shipping Weight 1,850 lbs (840 kg) 2,589 lbs (1,174 kg)
Floor Loading
Per Footprint
2,256 lbs/ft
2
(11,014 kg/m
2
)
15,298 kg/m
2
(3,133 lbs/ft
2
)
Clearance
FRONT: 43 7/16 in. (1,100 mm)
BACK/SIDE: 0 in. (0 mm)
TOP: 15 3/4 in. (400 mm)
Heat Rejection
27,620 BTU/h
(6,960 kcal/h)
*IP20: Foreign objects that are 12 mm (15/32”) or larger are prevented from entering the enclosure of the UPS.