Toshiba RC803A-HP1 Power Supply User Manual


 
TOSHIBA
6F9E0090
(4) When the Dower source is
aDDlied.
the relay is excited and the
OutDut
contact’s states are reversed. The
relationshiD
between
the input signal end the
outDut
contacts are shown
in
Table 2.
Check this relationship during the test.
Table 2
(5)
If no
Droblea
is found when the Dower source is
aDDlied.
turn
the rain circuit switch ON and
Derforg
the following checks:
(a)
In the case of a motor load
If the set
start-up
tiae
delay is too short, the relay
say
be actuated. In such a case, reset the detection delay
tiae
adjusting knob accordingly. After the start-up
tiae
delay
has
exDired.
apply current above the set detection value
to
confirm
that the relay functions (after the
resoonse
delay
tile),
In addition, check that the detection
indicating
lamp
lights at the
sale
time the relay
ODerates.
-
14-