TOSHIBA
6F9E0090
WEHA
AC
Rating
Designation
B300
Inductive load
t-K&-
120
AC
240
24
DC 120
240
ITEH SPECIFICATIONS
Hysteresis
AgDrox.
10X of
ooerating
value.
Power consumption
oDperating
Power
3.5VA
olnput
Circuit
D.lVA
(when 5A is
applied)
Height
.75kg
(1.7
lb)
I
Break Continuous
5A SA
(p.f.-0.4)
3A SA
_--_________________-----------------.
0.3A
!iA
O.l!iA
(L/R=15ms)
5A
O.lA
5A
3.
DescriDtion
of
Ooeration
When the detected current exceeds the detection circuit
operating level, the detection delay timer is actuated. If
over-
current is continuously detected for more then the detection delay
time set value, the overcurrent response delay timer is actuated.
Then, if overcurrent is detected when the
resDonse
delay timer has
elapsed, the overcurrent relay is actuated.
If current drops below the undercurrent detection set
ValUe,
the
resgonse
delay timer is actuated, and after the set tile has
exoired,
the undercurrent detection relay is actuated. In the case
of undercurrent detection, the detection delay timer is not actuated.
-5-