19
1. Configure your UPS’s input and output: Put your UPS power module into setup mode by holding down both of its scroll buttons (
A
and
B
) at once. Scroll through the setup options (using
A
or
B
) and select the appropriate setting for each of the following options using
the “SELECT” button
B
.
• Input & Output Voltage: Select 200, 208 or 240 VAC.
• Output Frequency: Your UPS will autoselect 50 or 60 Hz to match the input.
• Economy Mode: Your UPS can provide on-line operation with zero transfer time. It can also operate in a more energy-efficient
line-interactive mode. Select Economy On to put the UPS in line-interactive mode. Select Economy Off to put the UPS in on-line
mode.
• After you have set these options, “exit” the setup mode with the scroll button
A
, then exit bypass mode by holding the ON
button
C
down until you hear a beep.
2. Turn input to the UPS ON: If the UPS power module is connected to a transformer module, turn the tranformer module’s AC-to-
UPS and Output Circuit Breakers
D
on. Turn the UPS power module’s Input Circuit Breaker
E
on. Press the UPS power module’s ON
button
C
until you hear a beep to begin inverter operation. If your AC input is not providing power normally, you may “cold start” your
UPS from battery. (Your battery must be at least partially charged for this operation to succeed.) Press and hold the ON
C
button until
you hear a beep to start your UPS in ON BATTERY mode. Note that some electronic equipment may draw more amps during startup;
when starting from battery, consider reducing the initial load on the UPS. Your UPS will perform a brief self-test and show the results on
the LCD Display
F
. See “Startup Self-Test” in the “Operation” section for the display sequence.
3. Turn UPS output ON: Turn the UPS power module’s Output Circuit Breaker
G
ON. If the UPS is connected to a transformer module, turn
the transformer module’s Manual Bypass Switch
H
from BYPASS to NORMAL and its Output Circuit Breaker ON. Your UPS will now
provide power to connected equipment.
4. To turn the UPS power module and transformer module OFF: Press the UPS power module’s OFF button
I
until you hear a beep.
Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display
F
will show BYPASS
MODE. Turn the UPS power module’s Input and Output Circuit Breakers (
E
and
G
) OFF. If the UPS is connected to a transformer module,
turn the transformer module’s power AC-to-UPS and Output Circuit Breakers
D
OFF. Your load will no longer be energized, and the
LCD Display
F
will be dark.
Power ON/OFF (6kVA and 10kVA models only)
NORMAL
BY
PAS
S
N
O
R
M
A
L
B
Y
PA
S
S
6kVA Models
10kVA Models
D
E
G
H
E
G
H
6kVA & 10kVA Models
(Front Panel)
D
F
C
A
B I