10 – Display and Confi guration (continued)
10-7 UPS System Setup Menu
Press the enter button ( ) to select “UPS SETUP” from the main
menu.
Accessing the UPS system setup menu requires a password. From
the login screen, press the enter button ( ) to select whether
to log in as an administrator or a user. Administrators can view
and change all UPS system parameters; regular users can view
all parameters, but can only change a few basic parameters. Only
qualified service personnel should log in as the administrator.
The password consists of 4 numerals. Press the scroll down button
( ) or the scroll up button ( ) to select the first numeral, then
press the enter button ( ) to enter the numeral choice. After
entering the last numeral, press the enter button ( ) to confirm
the password choice. The default user password is 0000. The
default administrator password is 0000. Only qualified service
personnel should have access to the administrator password. See
Section 10-11 for instructions on changing the passwords.
After the correct password has been entered, the LCD screen will
show the UPS system setup menu.
10-8 Bypass Setup Menu
Enter the UPS system setup menu as described in Section 10-7.
Use the scroll buttons (
, ) to move the cursor to “BYPASS
SETUP”, then press the enter button (
).
Use the scroll buttons ( , ) and the enter button ( ) to select
“VOLTAGE RANGE” or “FREQUENCY RANGE”.
1
1
2
2
3
4
1
2
3
1
4
2