7-4
Alarm Configuration
Email Message: Enables/Disables email notification for this alarm. (Default = On.)
Note: The Email Message parameter offers four different options: On, Off, On
(Copy to All Triggers) or Off (Copy to All Triggers). If either of the "Copy to All
Triggers" options is selected, then email notification for all other alarms will be
switched On or Off as indicated by this parameter. For example, If "Off (Copy
to All Triggers)" is selected, then Email notification will be disabled for all other
alarms too.
Address 1, 2, and 3: These parameters are used to select which of the three email
addresses defined via the "Email Messages" menu (see Section 5.9.11) will receive
the email alarm notification messages generated by this alarm. The Address
parameters can be used to select one, or any combination of the addresses defined
via the Email Messages menu. (Default = All On.)
Note: If Email addresses have been previously defined, then the text under the
parameters will list the current, user selected email addresses.
Subject: This parameter is used to define the text that will appear in the "Subject"
field for all email notification messages generated by the alarm.
(Defaults:
Over Current (Initial) = "Alarm: Over Current (Initial)"
Over Current (Critical) = "Alarm: Over Current (Critical)")
Load Shedding: Provides access to a submenu, which is used to configure
and enable the Load Shedding feature for the Over Current Alarm. When Load
Shedding is enabled and properly configured, the MPC will switch specific,
user-selected plugs On or Off whenever the current load exceeds the Alarm Set
Threshold value. If the Auto Recovery feature is enabled, the MPC can also return
these user-selected plugs to their prior status, when current load falls below the
Alarm Clear Threshold value. For more information on the Load Shedding Feature
and Auto Recovery, please refer to Section 7.1.1.