Xantrex Technology XDC 20-300SL Power Supply User Manual


 
Specifications and Characteristics
Electrical Specifications—Summary
Release 1.0 25
Table A.3Specifications for 80V to 600V Models
Table A.4Drift Specifications for 80V to 600V Models
Models 80–75 100–60 150–40 300–20 600–10
Output Ratings:
Output Voltage
1
Output Current
2
Output Power
1. Minimum output voltage is <0.3% of rated voltage at zero output setting.
2. Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.
0–80 V
0–75 A
6000 W
0–100 V
0–60 A
6000 W
0–150 V
0–40 A
6000 W
0–300 V
0–20 A
6000 W
0–600 V
0–10 A
6000 W
Line Regulation:
3
Voltage (0.01% of Vmax)
Current (0.05% of Imax)
3. For input voltage variation over the AC input voltage range, with constant rated load.
8mV
37.5 mA
10 mV
30 mA
15 mV
20 mA
30 mV
10 mA
60 mV
5mA
Load Regulation:
4
Voltage (0.05% of Vmax + 5 mV)
Current (0.1% of Imax + 20 mA)
4. For 0–100% load variation, with constant nominal line voltage.
45 mV
95 mA
55 mV
80 mA
80 mV
60 mA
155 mV
40 mA
305 mV
30 mA
Output Noise (0–20 MHz):
Voltage (p–p) 100 mV 100 mV 150 mV 250 mV 350 mV
Output Ripple (rms):
Voltage
Current
5
5. Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.
15 mV
320 mA
20 mV
230 mA
20 mV
120 mA
30 mV
50 mA
80 mV
25 mA
OVP Adjustment Range:
(0% to 110% of Vmax) 0–88 V 0–110 V 0–165 V 0–330 V 0–660 V
Efficiency:
6
6. Typical efficiency at nominal input voltage and full output power.
0.89 0.90 0.90 0.91 0.91
Models 80–75 100–60 150–40 300–20 600–10
Drift (30 minutes):
1
Voltage (0.04% of Vmax)
Current (0.6% of Imax)
1. Maximum drift over 30 minutes with constant line, load, and temperature, after power on.
32 mV
450 mA
40 mV
360 mA
60 mV
240 mA
120 mV
120 mA
240 mV
60 mA
Drift (8 hours):
2
Voltage (0.02% of Vmax)
Current (0.04% of Imax)
2. Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.
16 mV
30 mA
20 mV
24 mA
30 mV
16 mA
60 mV
8mA
120 mV
4mA
Temperature Coefficient:
3
Voltage (0.04% of Vmax/°C)
Current (0.06% of Imax/°C)
3. Change in output per °C change in ambient temperature, with constant line and load.
32 mV
45 mA
40 mV
36 mA
60 mV
24 mA
120 mV
12 mA
240 mV
6mA
TM-XDSL-01XN.book Page 25 Tuesday, November 5, 2002 3:22 PM