AEG PROTECT B. 1500 Power Supply User Manual


 
15
3.4 Technical Data
Model power
PROTECT B. 750 750 VA / 500 W
PROTECT B. 1000 1000 VA / 700 W
PROTECT B. 1500 1500 VA / 1050 W
PROTECT B. 2000 2000 VA / 1340 W
PROTECT B. 3000 3000 VA / 2100 W
UPS Input
Rated output voltage 220 / 230 / 240 Vac
Input voltage range 154 / 161 / 168 Vac ± 4%
(wide)
176 / 184 / 192 Vac ± 4%
(standard) until
264 / 276 / 288 Vac ± 4%
Frequency (autom. detection) 50 / 60 Hz ± 5 Hz
> 40 Hz (generator mode)
Curr. consumption (full-load)
PROTECT B. 750 5 A
PROTECT B. 1000 8 A
PROTECT B. 1500 10 A
PROTECT B. 2000 10 A
PROTECT B. 3000 16 A
Connection IEC power connector
(IEC 320)
USP output
Rated output voltage / 220 / 230 / 240 Vac
AVR-technology
Rated output voltage in ± 5 %
battery mode
Frequency in battery mode 50 Hz / 60 Hz ± 0.1 Hz