AEG PROTECT B. 1500 Power Supply User Manual


 
35
operating stag has been reached (pos. 7 p. 3).
In case anything different occurs, please
follow the instructions in Chapters 6.2 / 6.3.
i
Please shut down the entire system if you cannot
solve any problems which occur. Please contact
our hotline (see page 4).
5. When the LINE MODE display is lit, switch
on your loads one after the other. Note the
maximum permitted UPS load when doing
this (pos. 9 fig. p. 42).
In particular, bear in mind the considerable power
consumption of loads such as laser printers, large CRT
monitors and the like which can quickly lead to a UPS
overload.
5.4.2 Configuration
To reconfigure the internal UPS setup options, follow the
procedure as below:
1. Press the Configure
button more than three
seconds. Then UPS will transfer from configure mode
to “output voltage mode” showing the value by a
flashing LED at 220 Vac, 230 Vac or 240 Vac.
2. Press the Configure
button more than one
second, the UPS allows you to select the “output
voltage mode” one by one.
3. After selecting the mode, press the Enter
button
more than three seconds, the “output voltage mode”
is configured.
4. UPS will automatically transfer from configure mode
to “operating mode” displayed by a flashing LED
beside NORMAL, GENERATOR or WIDE RANGE.
5. Press the Configure
button more than one
second; the UPS will allow you to select the “operating
mode” one by one.