5.0 Operation
5.2.5 UPS Diagnostics menu (continued)
This screen shows the firmware instruction set revision for
the EUs display microprocessor.
This screen shows the number of Battery Packs reporting
that their voltage level has reached the proper float
voltage.
This screen shows the UPSs battery voltage. The accuracy
of this measurement is ±5% of the full scale value of
68Vdc.
This screen shows the cause of the last transfer to on-
battery operation. This information is updated each time
the UPS transfers to on-battery.
If the UPS transferred to on-battery operation because
of a mains voltage notch or spike, the display reports the
cause as notch/spike.
If the UPS transferred to on-battery operation because
of an unacceptable rate of change in the output voltage,
the display reports the cause as dV/dt.
If the UPS transferred to on-battery operation to
maintain proper output voltage regulation in response to
high or low mains voltage, the display reports the cause
as HiLineV or LoLineV.
If the UPS transferred to on-battery operation to
conduct battery tests, the display reports the cause as Self
test.
This screen shows the rms current drawn by the UPSs
load in Amps. The accuracy of this measurement is ±5% of
the full scale value of 35 Amps.
This screen shows the Volt-Amps drawn by the UPS's load
as a percent of full rated capacity. The accuracy of this
measurement is ±5% of the full scale value of 105%.