American Power Conversion POWERCELL Power Supply User Manual


 
Page 31
10.0 Specifications
9.1 Input
Nominal input voltage: single phase 120 Vac.
Nominal input frequency: 60 Hz.
9.2 Transfer Characteristics
Frequency limits for on-line operation: 60 Hz, ±5%.
Low input voltage limit for on-line operation: 103 Vac.
9.3 Output Characteristics
Maximum load: 250 VA or 170 W, 400 VA or 250 W, and 600 VA or 400 W for
models PERSONAL, PROFESSIONAL, and NETWORK respectively.
Nominal output voltage: 115 Vac, ±5%.
Frequency regulation: 60 Hz, ±3% Hz unless synchronized to the utility.
Waveshape: stepped approximation to sine wave, peak and rms values equiva-
lent to the utility.
Protection: electronically overcurrent and short circuit protected, overload
shutdown is latched.
9.4 Battery and charger
Battery type: maintenance free lead-acid, sealed and leakproof.
Typical service life: 3-6 years, dependent on number of discharges, temperature.
Low battery signalling: audible tone, computer interface port (NETWORK).
Recharge time: 6 to 10 hours, dependent on load and length of utility outage.
9.5 Surge and noise suppression
Surge energy rating: 240 Joules (one time, 10/1000µs waveform).
Surge current capability: 6500 Amp peak (one time, 8/20µs waveform).
Surge response time: 0 ns (instantaneous) normal mode, < 5 ns common mode.
Noise filter: full time EMI/RFI suppression, 100 kHz to 10 MHz.
9.6 Operating environment and physical dimensions
Operating Environment: 0°C - 40°C (32°F - 104°F); 0 - 95% RH, non condensing.
Size: 6.0" H x 3.4" W x 13.1" D (15 cm x 9 cm x 33 cm) for the PERSONAL and
PROFESSIONAL; 6.6" H x 4.7" W x 14.2" D (17 cm x 12 cm x 36 cm) for the
NETWORK.
Weight: 10 lb (4.6 kg), 18 lb (8.2 kg) and 25 lb (11.3 kg) for the PERSONAL,
PROFESSIONAL, and NETWORK. Add 2 lb (1 kg) for shipping.