American Power Conversion S10 Power Supply User Manual


 
2-18
GO TO BATTERY IF > XXXV Setting – lets you set a high voltage threshold for
the unit, which will force it to switch to power from the Internal Battery Pack once
the threshold has been reached. The settings range is from 134 to 144 volts
(Figure 25).
Figure 25. GO TO BATTERY IF > XXXV Setting Screen
GO TO BATTERY IF < XXXV Setting (not shown) – lets you set a low voltage
threshold for the unit, which will force it to switch to power from the Internal Battery
Pack once the threshold has been reached. The settings range is from 90 to 100
volts.