APC 1609 Power Supply User Manual


 
10
Storage, Maintenance, Transport
Storage, Maintenance, Transport
Storage
Store the UPS covered in a cool, dry location with the batteries fully charged.
At 5° to 86° F (–15° to 30° C), charge the UPS battery every six months.
At 86° to 113° F (30° to 45° C), charge the UPS battery every three months.
Replacing the Battery Module
This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated
from electrical hazards. You may leave the UPS and connected equipment on during the replacement
procedure.
Ensure battery replacement every 2-4 years.
Standard (40C) battery; Allen-Bradley catalog number: 1609-500SBAT.
High Temperature (50C) battery; Allen-Bradley catalog number: 1609-500HBAT.
Once the batteries are disconnected the connected equipment is not protected from power outages.
Refer to the appropriate replacement battery installation guide for battery module installation instructions. See
your dealer or contact Rockwell Automation at 440-646-5800 for information on replacement battery modules.
Be sure to deliver the spent battery(s) to a recycling facility or ship it to the address specified
in the replacement battery literature.