APC 175kW Power Supply User Manual


 
150/175kw Modular PDU Installation20
Note: Circuit breakers and conductor ampacity are derated in accordance with the
National Electrical Code.
Distribution Transformer
Model
PDPM150G6F PDPM150L6F PDPM175G6H
Size 150 kVA 150 kVA 175 kVA
Type Delta/Wye Delta/Wye Delta/Wye
Input voltage 480V 600V 480V
Input current 180 A 150 A 214 A
Output voltage 208Y/120V
208Y/120V 415Y/240V
Output current 399.72 A 399.72 A 243.47
Thermal sensing 180 NC 180 NC 180 NC
Weight 455 kg (1003 lb) 500 kg (1102 lb) 560 kg (1235 lb)
Efficiency 98.2% min. 98.2% min. 98.5% min.
Frequency 60 Hz 60 Hz 60 Hz
Noise < 55 db @ 1 m < 55 db @ 1 m < 55 db @ 1 m
Environment and Compliance
Temperature Operating: -5 to +40°C (23 to 104°F)
Storage: -25 to +65°C (-13 to 149°F)
Humidity Operating: 0 to 95%, non-condensing
Storage: 0 to 95%, non-condensing
Elevation 3000 m (9,842.5 ft)
Certification UL and cUL
Conditional Short-Circuit
Current Rating (I
CC
)
10 kA*
* The Conditional Short-Circuit Current Rating was not evaluated by
Underwriters Laboratories.