APC 175kW Power Supply User Manual


 
5150/175kw Modular PDU Installation
Installation
Electrical Safety
SAVE THESE INSTRUCTIONS!
This document contains important instructions that should be followed during installation of the 150/
175kW Modular Power Distribution Unit (PDU).
Inrow Installation
Maintain 36” hot aisle spacing.
DANGER
HAZARD OF ELECTRIC SHOCK
Only certified electricians are authorized to connect power to the PDU.
The PDU must be installed in accordance with the National Electrical Code or
the Canadian Electrical Code and all applicable local codes.
To prevent arcing when removing a Power Distribution Module (PDM) from
the panel, set all circuit breakers on that module to OFF (open).
Failure to follow these instructions can result in death or serious injury.
CAUTION
UNPROTECTED OUTPUTS
Remove cover plates from the unit before cutting holes for power cable access. Metal
shavings can cause serious equipment damage. A metal punch can be used to make
the holes in the plates.
Failure to follow these instructions can result in injury or equipment damage.
Hot Aisle
pdx0849a