APC ACRC103 Computer Accessories User Manual


 
17InRow RC Installation
Connect piping
See “Piping Diagrams,” beginning on page 8, for recommended valve, flexible adapter, and
strainer installation locations.
1. Route all piping
1
to the InRow RC in compliance with all local and national codes.
Note: Circuit setters are required to regulate the flow of chilled water to each piece of
equipment. When a CDU is used in conjunction with the equipment, circuit setters are
not required, as the CDU provides the flow-regulating function.
Note: The figure shows a top piping installation with a PEX fitting. Bottom piping
installations or rigid piping fittings are handled similarly.
2. Disassemble the union on the entering or exiting water line:
a. Remove the nut
3
from the body
6
.
b. Remove the disc
4
and gasket
5
. Save the gasket.
c. The disc
4
prevents water flow through the union.
Discard the disc
4
.
3. Repeat step 2 for the union on the other water line.
4. Assemble the union on the entering or exiting water line:
a. Use thread sealant and thread sealing tape in accordance
with local and national codes.
b. Slide the nut
3
onto the fitting
2
.
c. Seat the gasket
5
into the body
6
.
d. Tighten the body
6
onto the nut
3
, using a properly-
sized open end wrench.
5. Repeat steps 1 through 4 for the union on the other water line.
na2239a