InRow RC Installation18
Condensate pump. The pump is factory-wired and piped
internally to the lower condensate pan. The pump is capable of
moving liquid a maximum of 15.2 m (50 ft), including a
maximum lift of 4.9 m (16 ft). For example, if your lift is 3 m
(10 ft), you have 12.2 m (40 ft) of usable run. The pump also
uses an on-board condensate high level float switch, which is
wired into the InRow RC alarm input for local and remote
alarm capabilities.
Condensate pump drain connection.
CAUTION
CONDENSATE DAMAGE
• Do not exceed the lift or the run length of the drain system.
• To prevent equipment damage from condensate, do not leave the condensate drain line
coiled inside the equipment. Route the condensate drain line out the top or bottom of the
equipment before operation.
Failure to follow these instructions can result in equipment damage.
na1575a
na2271a
Condensate drain line
Note: Sufficient PVC drain line is
supplied to route the drain to the
outside of the equipment. To route
the drain line to a remote drain,
obtain additional hardware.