APC MX28B-1200 Network Router User Manual


 
Revision B MX28B-1200 PRODUCT MANUAL
MX28B-1200/2400 13
5. INSTALLATION PROCEDURES
5.1 Preparation
5.1.1 Recommended Tools
= Standard selection of insulated hand tools.
= Proper tools for crimping the selected cable lugs.
5.1.2 Recommended Test Equipment
= Digital Multimeter
5.1.3 Equipment Inspection
Remove equipment from packing material and inspect for shipping damage to verify the safety
and operational suitability for the installation site. [Refer to Section 1.3]
5.1.4 Safety Precautions
***** WARNING *****
The MX28B dc power plant is supplied from a nominal 220V ac, 60 Hz source. Keep the ac
input enclosure cover in place when the system is operational or energized.
***** CAUTION *****
Handling or touching the controller boards located inside this unit without being electro
statically discharged (grounded to the frame) may cause extensive damage to the electronics.
Before touching or handling the controller boards, it is recommended that an ESD wrist
strap be utilized.
***** WARNING *****
Hazardous energy levels are present on bare conductors in the -48V dc distribution
connection area of the plant. Accidental shorting of distribution conductors can cause
arcing and high currents that can cause serious burns or other physical harm.
It is recommended that:
= Any jewelry, rings or watches be removed while working on this equipment.
= Handles of all wrenches, screwdrivers, cutters and pliers be insulated.
= Shafts of screwdrivers be wrapped in electrical tape or otherwise insulated.