APC MX28B-1200 Network Router User Manual


 
Revision B MX28B-1200 PRODUCT MANUAL
MX28B-1200/2400 29
MX28B-1200 +
STATUS ALARMS SYSTEM MODULES BATT PIN OEM
Figure 5-11 Control Unit Display
5.10.2 System Parameters Verification/Adjustment
The MX28B system control unit is delivered with pre-programmed parameter default settings.
A complete listing and description of all system configuration parameters as well as displayable
system status and information is provided in Section 6. Read Section 6 to gain an understanding
of and how to use the operational features provided by the MX28B dc power plant. As a
minimum, the following parameters should be verified and adjusted, if required, before
connecting batteries or loads to the power plant:
1) Battery Float Voltage - default = -54.00V dc (Check the manufacturer’s
recommendation for the batteries being used in the system.)
2) Battery Maximum Recharge Rate - default = 50A. (Bellcore specifications
recommend a maximum charging rate of battery capacity (in Ampere-hours) divided by
20 hours; check the manufacturer’s recommendation.)
3) System Voltage - measurement -54.00V dc (This is a measurement by the system of
the dc output bus voltage.)
4) LVD Option - default = “Enable” (If the MX28B does not have an LVD installed, this
should be changed to “Disable”.)
5) Rectifier Information - Check the rectifier information displays to verify that all
rectifiers installed can be viewed on the control unit display and that no rectifier alarms
are active.
Section 6 provides location information for these parameters and how to make changes if
required.
5.10.3 Full System Power Up
To complete a full system power up, perform the following steps
1) Turn OFF all the circuit breakers that supply ac power to the rectifiers in the MX28B dc
power plant.
2) Turn on the external circuit breaker from the battery to the power plant.
3) Turn on all the circuit breakers that supply ac power to the rectifiers in the MX28B dc
power plant.
4) Load circuit breakers and distribution fusses may now be turned on and inserted as
required.