Chapter 4: E2 Controller
Table 4-10. Factory default setpoints.
Parameter Default Value
Temperature Setpoint 72° F
Compressor Cut- in 74° F
Compressor Cut- out 72.3° F
Minimum Fan Speed 40%
Maximum Fan Speed 100%
Dehumidification Fan Speed 60%
Humidity Setpoint 45% RH
Dehumidify Cut-in 50% RH
Dehumidify Cut-out 47% RH
Figure 4-63. Set Passwords screen.
The second Service>Save Cfg menu screen allows you to set new passwords for entering the Control and Service menus.
4.5.5.10 Factory Menu
Figure 4-64. Factory Menu screen.
The Factory Menu loop may be accessed from the Service>Factory screen. You must enter the factory-level password to gain
access to the loop. Contact Black Box Tech Support for the password and for guidance when adjustments must be made at this
level.