Page 75
Chapter 4: E2 Controller
Figure 4-48. Fans will run at 60% of full speed during dehumidification.
If the Dehum Speed is set to 80%, the lower fan will run at 75% during dehumidification as it is limited by the maximum speed
setting for the lower temperature zone.
Figure 4-49. Lower fan will run at 75% of full speed during dehumidification (limited by the temperature zone maximum).
4.5.5.5 Options Menu Loop
Figure 4-50. Options Menu Loop screen.
From the Service>Options menu, you may press the Enter key to access a menu loop with screens used to set up and adjust
various options.
Control, Startup
Figure 4-51. Control, Startup screen.
The Service>Options>Control, Startup screen allows you to select the control method.
Standard = Temperature/Humidity Control
Dewpoint = Dewpoint Control