Bosch Appliances D9210C Network Router User Manual


 
10 en | Strike Profile Access Control Interface Module
F.01U.201.526 | 02 | 2011.10 Program Entry Guide Bosch Security Systems, Inc.
Blank Buzz Time is not programmed for this door.
1-240 The buzzer will sound for the amount of time programmed.
Enter the amount of time that strike, buzz and shunt activation will be prolonged if a door is
left open and the shunt time expires. At the end of the programmed extend time, the buzzer
will continue to buzz until the door is closed. In addition, if programmed, the point assigned
to the door will indicate a Trouble, Alarm or Fault at the command center.
This program item determines whether the strike will deactivate immediately upon physically
opening the door.
Yes Strike will deactivate when the door is opened after a valid access granted request.
No Strike will remain activated for the amount of the programmed strike time whether door is
opened or closed.
TO REDUCE FALSE ALARMS: We recommend that you maintain this programming item as
defaulted [YES]. This will help prevent the door from “bouncing” open and causing a false
alarm.
Use this program item to disable the strike, but still activate the programmed shunt time upon
a Request to Enter an area.
D# Extend Time
Default: 10
Selections: Blank, 1-30 seconds
NOTICE!
CLOSE DOOR # display on Command Center will not activate if no time (blank) is
programmed.
NOTICE!
Regardless of how the door point is programmed, the system will generate a Trouble Door
Left Open event while the system is disarmed and an Alarm Door Left Open event if the
system is armed and the door is held open beyond Extend Time. Door Closed Restoral events
are generated after the door is held open past Extend Time and the door has returned to
normal.
D# Deact On Open?
Default: No
Selections: Yes or No
NOTICE!
In order for this function to work a point needs to be assigned to the door.
D# RTEShunt Only?
Default: No
Selections: Yes or No