26
6.6 SIGNALIZATIONS
Eight signal LEDs (normally off) are provided:
a) Red LED
dA>
q Flashing when I
d
A > [I
ds
].
q Illuminated on tripping of the biased differential element : I
d
A > I
S
b) Red LED
dB>
q Flashing when I
d
B > [I
ds
].
q Illuminated on tripping of the biased differential element : I
d
B > I
S
c) Red LED dC>
q Flashing when I
d
C > [I
ds
].
q Illuminated on tripping of the biased differential element : I
d
C > I
S
d) Red LED
dvs
q Flashing during supervision time delay
q Illuminated on tripping of the CTs Supervision element.
e) Yellow LED
PROG/
I.R.F.
q Flashing during the programming of the parameters or in case of
Internal Relay Fault.
f) Red LED
Remote
Trigger
q Illuminated when the oscillography trigger input is activated
g) Red LED
Time
Sync.
q Illuminated when synchronization input is active
h) Yellow LED
BLOCK
INPUT
q Flashing when digital input B1 is activated
The reset of the LEDs takes place as follows
q
From flashing to off, automatically when the lit-on cause disappears.
q
From ON to OFF, by "ENTER/RESET" push button only if the tripping cause has disappeared.
In case of auxiliary power supply failure the status of the LEDs is recorded and reproduced when power supply
is restored.