Cooper Lighting M-LIB3 Switch User Manual


 
S150-34-1
35
6.20 ELECTRICAL CHARACTERISTICS
q REFERENCE STANDARDS IEC 60255 - EN50263 - CE Directive - EN/IEC61000 - IEEE C37
q
Dielectric test voltage IEC 60255-5 2kV, 50/60Hz, 1 min.
q
Impulse test voltage
IEC 60255-5 5kV (c.m.), 2kV (d.m.) – 1,2/50µs
q
Climatic tests
IEC 68-2
CE EMC Compatibility (EN50081-2 - EN50082-2 - EN50263)
q
Electromagnetic emission EN55022
q
Radiated electromagnetic field immunity test IEC61000-4-3 level 3 80-1000MHz 10V/m
ENV50204 900MHz/200Hz 10V/m
q
Conducted disturbances immunity test IEC61000-4-6 level 3 0.15-80MHz 10V/m
q
Electrostatic discharge test IEC61000-4-2 level 4 6kV contact / 8kV air
q
Power frequency magnetic test IEC61000-4-8 1000A/m 50/60Hz
q
Pulse magnetic field IEC61000-4-9
1000A/m, 8/20µs
q
Damped oscillatory magnetic field IEC61000-4-10 100A/m, 0.1-1MHz
q
Electrical fast transient/burst IEC61000-4-4 level 4 2kV, 5/50ns, 5kHz
q
HF disturbance test with damped oscillatory wave (1MHz
burst test)
IEC60255-22-1 class 3 400pps, 2,5kV (m.c.), 1kV (d.m.)
q
Oscillatory waves (Ring waves) IEC61000-4-12 level 4 4kV(c.m.), 2kV(d.m.)
q
Surge immunity test IEC61000-4-5 level 4 2kV(c.m.), 1kV(d.m.)
q
Voltage interruptions IEC60255-4-11 200ms
q
Resistance to vibration and shocks IEC60255-21-1 - IEC60255-21-2 – 10-50Hz – 1g
CHARACTERISTICS
q
Accuracy at reference value of influencing factors 2% Rated Input for measure
2% +/- 10ms for times
q
Average power supply consumption 8.5 VA
q
Output relays rating 5 A; Vn = 380 V
A.C. resistive switching = 1100W (380V max)
make = 30 A (peak) 0,5 sec.
break = 0.3 A, 110 Vcc,
L/R = 40 ms (100.000 op.)
q
Operation ambient temperature -10°C / +55°C
q
Storage temperature -25°C / +70°C
q
Humidity 93% Without Condensing
The performances and the characteristics reported in this manual are not binding and are subject to change without notice