Crestron DIN-8SW8 DIN Rail High-Voltage Switch
Operation
NET ID
Use the NET ID buttons to change the Net ID of the DIN-8SW8. For
information on Net ID, refer to “
Identity Code” which starts on page 10.
Manual
Control
The state of each output can be manually controlled from the front panel.
To toggle the output between off and on, tap the appropriate button
(1 – 8). The corresponding LED illuminates and the output state is shown
on the NET ID display (“oF” for off, “On” for on) for two seconds after
the button is released.
NOTE: The control system program may change the settings if the
Override mode is not enabled.
Override
Mode
The Override mode overrides the control system program and sets all of
the output states to the stored override values. For instructions on saving
override settings, refer to “
Save Override Settings” on page 22.
To enable Override mode, press and release the OVR button. The OVR
LED flashes slowly.
NOTE: If the Override mode was enabled from an external device (i.e.
a contact closure is present on the OVERRIDE terminals), the OVR
LED will flash quickly. Pressing the OVR button has no effect.
To disable Override mode, press the OVR button again. The OVR LED
extinguishes and the outputs return to the states set by the control system
program.
NOTE: If override states have not been stored, the factory default
override state is all loads on.
Operations & Installation Guide – DOC. 6666A DIN Rail High-Voltage Switch: DIN-8SW8 • 21