Crestron electronic DIN-HUB Network Card User Manual


 
Crestron DIN-HUB DIN Rail Cresnet
®
Distribution Hub
Cresnet units are to be daisy-chained on the run, the Cresnet power usage
of each network unit to be daisy-chained must be added together to
determine the Cresnet power usage of the entire chain. If the unit is
home-run from a Crestron system power supply network port, the
Cresnet power usage of that unit is the Cresnet power usage of the entire
run. The wire gauge and the Cresnet power usage of the run should be
used in the following equation to calculate the cable length value on the
equation’s left side.
Cable Length Equation
L = Length of run (or chain) in feet
R = 6 Ohms (Crestron Certified Wire : 0.75 MM (18 AWG))
P = Cresnet power usage of entire run (or chain )
2
L <
40,000
R x P
Where:
Make sure the cable length value is less than the value calculated on the
right side of the equation. For example, a Cresnet run using 0.75mm
2
(18 AWG) Crestron Certified Wire and drawing 20 watts should not have
a length of run more than 101 meters (333 feet). Cresnet-HP cannot be
used.
NOTE: All Crestron certified Cresnet wiring must consist of two
twisted pairs. One twisted pair is the +24V conductor and the GND
conductor and the other twisted pair is the Y conductor and the Z
conductor.
Strip and Tin
Wire
When daisy-chaining Cresnet units, strip the ends of the wires carefully
to avoid nicking the conductors. Twist together the ends of the wires that
share a pin on the network connector and tin the twisted connection.
Apply solder only to the ends of the twisted wires. Avoid tinning too far
up the wires or the end becomes brittle. Insert the tinned connection into
the Cresnet connector and tighten the retaining screw. Repeat the
procedure for the other three conductors.
Reference Documents
The latest version of all documents mentioned within the guide can be
obtained from the Crestron website (
www.crestron.com/manuals). This
link will provide a list of product manuals arranged in alphabetical order
by model number.
Operations & Installation Guide – DOC. 6671A DIN Rail Cresnet Hub: DIN-HUB 15