© 2010 CyberPower Systems (USA), Inc. All Trademarks are property of their owners.
Page: 16 of 17
Table 7: Specifications
6 SPECIFICATIONS
Model Number CS150U48V3
Input:
Rating Voltage/Frequency 100 - 240V / 50 - 60Hz
Input Voltage Range 90 - 264Vac
Frequency Range 47 - 63Hz
P.F. > 0.9 at Rating Voltage and Max Load
Output:
Output Power Continuous 150W
Output Power Max 170W, 10sec Max.
Output Voltage Range 42V - 58Vdc
Output Current (max Load) 3.1A Nominal
Ripple < 30mVrms
Noise < 120mVp-p
Efficiency > 85% at Rating Voltage and Max Load
Output Connection
7-Pin communication signals connector
(DECA ME030-5007), Max 12AWG
Battery
Battery Type Sealed, Maintenance Free Lead-Acid Battery
Numbers of Battery 7.2 (7) AH/12V (8-standard, 4-factory orderable option)
Replaceable Yes
Surge Protection and Filtering
Lightning / Surge Protection GR-1089-CORE Sect 4
Warning Diagnostics
AC (AC/Battery Mode Indicator), Output (Output On/Off
Indicator), Battery (Battery Missing/Replacement Indicator)
Management
Auto-Charge Yes
Communication Interface On Battery, Replace Battery, Battery Missing, Low Battery
Physical
Maximum Dimensions (W*D*H) 389mm x 230mm x 400mm
Weight 28kg (with 8pcs battery)
Environmental Specifications
Operating Temperature -4°F to 131°F (-20°C to 55°C)
Operating Humidity 0 to 95% non-condensing within enclosure
Max Operating Elevation 10,000ft (3,000m)
Max Storage Elevation 50,000ft (15,000m)
-4°F to 131°F (-20°C to 55°C)
Compliance
CSA/UL 60950, EN 60950, EN 55022 Class B, FCC Part
15 Class B, GR-63 Sect 4.2 Fire Resistance,
GR-1089 Sect 3 Emissions, Sect 4 Lightning and AC
Power Fault, Sect 7 Electrical Safety.
Storage Temperature
Indicators