PD-01 PROFIBUS-DP Module
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
14
0101: 5th speed
0110: 6th speed
0111: 7th speed
1000: 8th speed
1001: 9th speed
1010: 10th speed
1011: 11th speed
1100: 12th speed
1101: 13th speed
1110: 14th speed
b11-b8
1111: 15th speed
b12 1: Enable b11-b6
00: No function
01:Operation command controlled by PU
10:Operation command by Pr. setting
b14-b13
11:Switch between PU and Pr. setting
b15 Not used
NOTE:
Table above is for reference only, please check VFD series Drives user manual for
details. The control word that is mapping to the address of VFD series Drives can be
carried out by PD-01, so the bit assignments in the user manual of VFD series Drives is valid.
Status word (data from VFD series Drives to DP)
00: RUN LED light off, STOP LED light up (Drive Stop)
01: RUN LED blink, STOP LED light up (Drive Decelerate
during the drive stopping)
10: RUN LED light up, STOP LED blink (Drive standby)
b1-b0
11: RUN LED light up, STOP LED light off (Drive Run)
b2 1: JOG is active
00: REV LED light off, FWD LED light up (Forward)
01: REV LED blink, FWD LED light up (Reverse to Forward)
10: REV LED light up, FWD LED blink (Forward to Reverse)
b4-b3
11: REV LED light up, FWD LED light off (Reverse)
b5 1: Reserved parameters opened
b6 Reserved
b7 Reserved
b8 1: Main frequency controlled by communication
b9 1: Main frequency controlled by external terminal (EXT)
b10 1: Operation command controlled by communication (PU)
b11 1: Parameters have been locked
b12 Copy command enable
b15-b13 Reserved