PD-01 PROFIBUS-DP Module
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
28
Edit the user parameters in S7 Step hardware configuration tools shown below:
NOTE:
Please do not set d_state to 1 when the address in Data Output 1 ~ Data Output 4 is
non-continuous to avoid Parameterization error and IO disconnect. The PD-01 just check the
address starting from Data Output 1 to Data Output [dout_len-1], in other words, if the
address in Data Output 1 ~ Data Output 3 is continuous, but the address in Data Output 4 is
not, and dout_len is 0x0003, then the check still can pass.