Delta Electronics VFD-XXXM Network Card User Manual


 
English-17
Parameter Explanation Settings
Factory
Setting
Customer
Pr.119 Differential Time (D) 0.00 to 1.00 sec 0.00
Pr.120
Integration’s Upper
Bound Frequency
00 to 100 % 100 %
Pr.121 One-Time Delay 0.0 to 2.5 sec 0.0
Pr.122
PID Frequency Output
Command Limit
00 to 110 % 100
Pr.123
Feedback Signal
Detection Time
0.0: Disable
0.1 to 3600 sec
60.0
Pr.124
Feedback Signal Fault
Treatment
00: Warning and RAMP to stop
01: Warning and keep operating
00
Pr.125 Source of PID Set Point 0.00 to 400.0Hz 0.00
Pr.126 PID Offset Level 1.0 to 50.0 % 10.0
Pr.127
Detection Time of PID
Offset
0.1 to 300.0 sec 5.0
Pr.128
Minimum Reference
Value
0.0 to 10.0 V 0.0
Pr.129
Maximum Reference
Value
0.0 to 10.0 V 10.0
Pr.130
Invert Reference Signal
AVI (0-10V)
00: Not inverted
01: Inverted
00
Pr.131
Minimum Reference
Value (4-20mA)
0.0 to 20.0mA 4.0
Pr.132
Maximum Reference
Value (4-20mA)
0.0 to 20.0mA 20.0
Pr.133
Invert Reference Signal
(4-20mA)
00: Not inverted
01: Inverted
00
Pr.134
Analog Input Delay
Filter for Set Point
00 to 9999 (per 2ms) 50
Pr.135
Analog Input Delay
Filter for Feedback
Signal
00 to 9999 (per 2ms) 5
Pr.136 Sleep Period 0.0 to 6550.0 sec 0.0
Pr.137 Sleep Frequency 0.00 to 400.0 Hz 0.00
Pr.138 Wake Up Frequency 0.00 to 400.0 Hz 0.00
Pr.139
Treatment for Counter
Attained
00: Continue operation
01: Stop Immediately and display E.F.
00
Pr.140
External Up/Down
Selection
00: Fixed Mode (keypad)
01: By Accel or Decel Time
02: Reserved
00
Pr.141
Save Frequency Set
Point
00: Not Save
01: Save
01