Delta Electronics VFD-XXXM Network Card User Manual


 
English-18
Parameter Explanation Settings
Factory
Setting
Customer
Pr.142
Second Source of
Frequency Command
00: Keypad Up/Down
01: AVI (0-10V)
02: ACI (4-20mA)
03: Communication
04: Keypad potentiometer
00
115V/230V 370-450 Vdc 380.0
460V 740-900 Vdc 760.0
Pr.143 Software Braking Level
575V 925-1075 Vdc 950.0
Pr.144
Total operation time
(Day)
Read Only
Pr.145
Total operation time
(Minutes)
Read Only
Pr.146 Line start Lockout
00: Disable
01: Enable
00
Pr.147
Decimal Number of
Accel / Decel Time
00: One decimal
01: Two decimals
00
Pr.148 Number of Motor Poles 02 to 20 04
Pr.149
Gear Ratio for Simple
Index Function
4 to 1000 200
Pr.150
Index Angle for Simple
Index Function
00.0 to 360.0 180.0
Pr.151
Deceleration Time for
Simple Index Function
0.00 to 100.00 sec 0.00
Pr.152 Skip Frequency Width 0.00 to 400.0Hz 0.00
Pr.153 Bias Frequency Width 0.00 to 400.0Hz 0.00
Pr.154 Reserved
aPr.155
Compensation
Coefficient for Motor
Instability
0.0: Disable
0.1 to 5.0 (recommended setting d2.0)
0.0
aPr.156
Communication
Response Delay Time
0 to 200 (x500us) 0
aPr.157
Communication Mode
Selection
0: Delta ASCII
1: Modbus
1