SPECIFICATIONS
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
100
Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) (continued)
Nine- and Twelve-Slot Cabinet
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Heat
Dissipation
Recommended
Input Service
Output Current
(100/200V, 110/220V, 120/240V)
Input Current
(200V)
UPS
kVA/Watts
Optional
Chargers
0 12/10000 64A 60A, 56A, 50A 80A 1145W
(3.90 kBTU/hr)
1 12/10000 80A 60A, 56A, 50A 100A 1430W
(4.88 kBTU/hr)
2 12/10000 96A 60A, 56A, 50A 125A 1720W
(5.85 kBTU/hr)
3 12/10000 102A** 60A, 56A, 50A 125A 1995W
(6.75 kBTU/hr)
0 15/12500 80A 75A, 70A, 62.5A 100A 1430W
(4.88 kBTU/hr)
1 15/12500 96A 75A, 70A, 62.5A 125A 1720W
(5.85 kBTU/hr)
2 15/12500 102A** 75A, 70A, 62.5A 125A 1995W
(6.75 kBTU/hr)
0 18/15000 96A 90A, 84A, 75A 125A 1720W
(5.85 kBTU/hr)
1 18/15000 102A** 90A, 84A, 75A 125A 1995W
(6.75 kBTU/hr)
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external
battery cabinet XXXXX-Model/Batt4.