Eaton Electrical ASY0567 Power Supply User Manual


 
SPECIFICATIONS
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
101
Table 17. Model Specifications for Universal Power Modules (XXXXX-Model/03 and ASY-0674)
Three-Slot Cabinet
Optional
Chargers
UPS
kVA/Watts
Input Current for
200/208/220/230/240V*
Output Current for
200/208/220/230/240V
Recommended
Input Service*
Heat
Dissipation
NA 3/2100 14/13.5/13/12.5/12A 15/14.5/14/13/12.5A 25A 285W
(0.98 kBTU/hr)
Six-Slot Cabinet
CAUTION Do NOT install more than three power and/or battery charger modules in a 6-slot cabinet.
Optional
Chargers
UPS
kVA/Watts
Input Current for
200/208/220/230/240V
Output Current for
200/208/220/230/240V
Recommended
Input Service
Heat
Dissipation
0 3/2100 14/13.5/13/12.5/12A 15/14.5/14/13/12.5A 25A 285W
(0.98 kBTU/hr)
1 3/2100 30/29.5/29/28.5/28A 15/14.5/14/13/12.5A 40A 570W
(1.95 kBTU/hr)
2 3/2100 46/45.5/45/44.5/44A 15/14.5/14/13/12.5A 60A 860W
(2.93 kBTU/hr)
0 6/4200 28/27/26/25/24A 30/29/28/26/25A 40A 570W
(1.95 kBTU/hr)
1 6/4200 44/43/42/41/40A 30/29/28/26/25A 60A 860W
(2.93 kBTU/hr)
0 9/6300 42/40.5/39/37.5/36A 45/43.5/42/39/37.5A 60A 860W
(2.93 kBTU/hr)
Nine- and Twelve-Slot Cabinet
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Optional
Chargers
UPS
kVA/Watts
Input Current for
200/208/220/230/240V
Output Current for
200/208/220/230/240V
Recommended
Input Service
Heat
Dissipation
0 3/2100 14/13.5/13/12.5/12A 15/14.5/14/13/12.5A 25A 285W
(0.98 kBTU/hr)
1 3/2100 30/29.5/29/28.5/28A 15/14.5/14/13/12.5A 40A 570W
(1.95 kBTU/hr)
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external
battery cabinet XXXXX-Model/Batt4.