Eaton Electrical ASY0567 Power Supply User Manual


 
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
9
Chapter 2 Installation Setup
This chapter explains how to set up and install the Eaton 9170+
cabinets:
S Setup, including clearances and location requirements
S Caster cart installation (for 3- and 6-slot cabinets)
S Stabilizer bracket installation (for 12-slot cabinets)
S Rack-mount installation (for 3- and 6-slot cabinets)
S Floor anchor kit installation
S Moving the cabinets
Equipment Clearances
All cabinet sizes require the following clearances to allow for servicing
and adequate ventilation:
S Sides: 15.2 cm (6)
S Top and back: 30.5 cm (12)
S Front: 91.5 cm (36)
If flexible conduit connects the UPS to the service input and load
distribution panels, you may be able to gain access for servicing by
moving the UPS. If this is the case, you must still leave 30.5 cm (12)
clearance at the back and 15.2 cm (6) at the sides of the UPS for
ventilation.
NOTE Do not block the ventilation holes on each side and the back of the cabinet.
Nine- and 12-slot external battery cabinets may be installed with bases
tight against the UPS cabinet base and against each other. Six-slot
cabinets require 15.2 cm (6) of separation.