SPECIFICATIONS
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
103
Table 17. Model Specifications for Universal Power Modules (XXXXX-Model/03 and ASY-0674) (continued)
Nine- and Twelve-Slot Cabinet
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Heat
Dissipation
Recommended
Input Service
Output Current for
200/208/220/230/240V
Input Current for
200/208/220/230/240V
UPS
kVA/Watts
Optional
Chargers
4 9/6300 102A** 45/43.5/42/39/37.5A 125A 1995W
(6.75 kBTU/hr)
0 12/8400 56/54/52/50/48A 60/58/56/52/50A 80A 1145W
(3.90 kBTU/hr)
1 12/8400 72/70/68/66/64A 60/58/56/52/50A 100A 1430W
(4.88 kBTU/hr)
2 12/8400 88/86/84/82/80A 60/58/56/52/50A 125A 1720W
(5.85 kBTU/hr)
3 12/8400 102/102/100/98/96A** 60/58/56/52/50A 125A 1995W
(6.75 kBTU/hr)
0 15/10500 70/67.5/65/62.5/60A 75/72.5/70/65/62.5A 100A 1430W
(4.88 kBTU/hr)
1 15/10500 86/83.5/81/78.5/76A 75/72.5/70/65/62.5A 125A 1720W
(5.85 kBTU/hr)
2 15/10500 102/99.5/97/94.5/92A** 75/72.5/70/65/62.5A 125A 1995W
(6.75 kBTU/hr)
0 18/12600 84/81/78/75/72A 90/87/84/78/75A 125A 1720W
(5.85 kBTU/hr)
1 18/12600 100/97/94/91/88A** 90/87/84/78/75A 125A 1995W
(6.75 kBTU/hr)
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external
battery cabinet XXXXX-Model/Batt4.