Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
53
Chapter 5 Isolated Output Wiring Diagrams
NOTE This chapter is only for units manufactured before 2009.
The wiring diagrams in this section are unique and specific to
installations in which the output of the Eaton 9170+ UPS is galvanically
isolated from the input.
Figure 35 and Figure 36 describe output wiring configurations for various
output voltages. Use Table 9 to identify the wiring diagrams and connect
the output AC wiring to the proper Eaton 9170+ system power
terminals. You must also set the operating menu 4 2 4 for the required
output voltage as shown in the wiring configuration drawings.
NOTE Do NOT install more than seven power and/or optional battery charger modules in
the system.
NOTE In isolated-output installations, connect the UPS green and yellow neutral-to-ground
wire (N-G bond) to the UPS output terminal as illustrated in Figure 37 on page 55.
Table 9. Wiring Diagrams for Isolated Output (Split-Phase Power Modules Required)
UPS Input
Voltage
UPS Output
Voltage
Output Wires
External
Bypass
Wiring Diagrams
Input Output System
100/200
110/220
115/230
120/240
120/208*
100/200
110/220
115/230
120/240
120/240
L1, L2, N
Yes
Figure 17a on
page 30
Figure 35 on
page 54
Figure 38 on
page 57
No
Figure 17a on
page 30
Figure 35 on
page 54
Figure 39 on
page 58
120/208*
127/220*
120/208
127/220
L1, L2, N
Yes
Figure 17a on
page 30
Figure 36 on
page 54
Figure 40 on
page 59
No
Figure 17a on
page 30
Figure 36 on
page 54
Figure 41 on
page 60
* External bypass switch, if installed, must be Break-Before-Make.