Emerson 15-90KVA Power Supply User Manual


 
Electrical Connections—UPS
18
3.2.4 UPS Input Configuration
By default, the Liebert
®
APM
ships with internal links installed between the bypass input and main
(rectifier) input (single input configuration see Figure 48).
Figure 4 shows the Liebert APM in a split bypass (single source dual-input) configuration. In this
configuration, the static bypass and the maintenance bypass lines are supplied by the same source
using separate feeds. Both feeds must be protected externally with properly sized protective devices.
To wire the Liebert APM as a single source dual-input UPS, remove the links and wire the bypass
feed to the bypass busbars, then wire the main feed to the main busbars (see Figure 6).
Figure 4 Single UPS block diagram—dual input single source configuration
NOTES
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. A neutral is required from the system AC input source. A full
capacity neutral conductor is recommended. Grounding
conductors are recommended.
4. Bypass and rectifier inputs and output cables must be run
in separate conduits.
5. Control wiring must be run in separate conduits.
6. Optional 54-pole, 225A for 45kVA frame only or optional 54-pole,
400A for 90kVA frame only.
7. Customer must supply shunt trip breaker with 120V coil.
BIB - Bypass Isolation Breaker
MBB - Maintenance Bypass Breaker
MIB - Maintenance Isolation Breaker
* External Overcurrent Protection
by others
Field-Supplied Wiring
UAM01023
Rev. 3
Bypass Distribution Cabinet
* Bypass
AC Input
4-Wire + GND
* Rectifier
AC Input
4-Wire + GND
See Note 7
BIB
MBB
MIB
Static Bypass
UPS Cabinet
Battery
Optional
54-Pole
See Note 6
AC Output
208V
4-Wire + GND