HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
8.8 Electrical Characteristics (System Performance)
Table 8-8 Electrical characteristics (system performance)
Power rating (kVA)
Item Unit
160
(6-pulse)
160
(12-pulse)
200
(6-pulse)
200
(12-pulse)
300
(6-pulse)
300
(12-pulse)
400
(6-pulse)
400
(12-pulse)
No load losses kW 2.75 3.30 3.50 4.15 3.90 4.65 4.70 6.51
Full load losses
(100%)
kW 9.63 11.89 11.12 13.91 19.33 21.8 28.2 31.6
8.9 Electrical Characteristics (ECO Mode)
Table 8-9 Electrical characteristics (ECO mode)
Power rating (kVA)
Item Unit
160
(6-pulse)
160
(12-pulse)
200
(6-pulse)
200
(12-pulse)
300
(6-pulse)
300
(12-pulse)
400
(6-pulse)
400
(12-pulse)
Full load
losses (100%)
kW 2.97 3.52 3.55 4.20 5.23 5.91 7.10 8.96