Emerson GXT5000R-208 Power Supply User Manual


 
6
Auxiliary 120V / 400VA Power
The GXT5VBATTW120 battery cabinet also provides a transformer to provide up to 400VA of
120V power.
Dynamic Bypass
The GXT5000R-208 provides an alternate path for utility power to the connected load in the
unlikely event of a UPS malfunction, such as overload, overtemperature, or an internal UPS
failure. If a malfunction does occur, the UPS automatically transfers the connected load to
bypass. Bypass operation is indicated by an alarm and illuminated Bypass LED (other LEDs
also may be illuminated to indicate the diagnosed problem). To manually transfer the con-
nected load from the inverter to bypass, press the Standby button once.
NOTE
The bypass power path does NOT protect the connected equipment from
disturbances on the utility supply, such as spikes, sags, and failure.