25
BATTERY CABINET SPECIFICATIONS
GXT5VBATTW120
MODEL NUMBER GXT5VBATTW120
DIMENSIONS: inches (mm)
Unit: W x D x H 16.1 x 23.6 x 5.1 (410 x 600 x 130)
Shipping: W x D x H 23.2 x 31.1 x 12.8 (590 x 790 x 325)
WEIGHT: lbs (kg)
Unit 121.7 (55.2)
Shipping 132.3 (60.0)
AC PARAMETERS – AUXILIARY AC POWER
Nominal AC Input 208 VAC, 50/60 Hz, 400 VA, Single-Phase
Nominal AC Output 120 VAC, 50/60 Hz, 400 VA, 0.75 PF (Power Factor)
Output Receptacles 5-15R (2)
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Qty. x Battery Voltage x Battery Rating 20 x 12 VDC x 28 watts per cell (10-minute rate)
Battery Mfg./ Part # Yuasa 28-12
ENVIRONMENTAL
Operating Temperature +32°F to +104°F (0°C to +40°C)
Storage Temperature +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating
AGENCY
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A
GXT5VBATT
MODEL NUMBER GXT5VBATT
DIMENSIONS: inches (mm)
Unit: W x D x H 16.1 x 18.5 x 5.1 (410 x 470 x 130)
Shipping: W x D x H 23.2 x 31.1 x 12.8 (590 x 790 x 325)
WEIGHT: lbs (kg)
Unit 107.3 (48.7)
Shipping 116.6 (52.9)
BATTERY PARAMETERS
Type Valve regulated, nonspillable, lead acid
Qty. x Battery Voltage x Battery Amp Rating 20 x 12 VDC x 28 watts per cell (10-minute rate)
Battery Mfg./ Part # Yuasa 28-12
ENVIRONMENTAL
Operating Temperature +32°F to +104°F (0°C to +40°C)
Storage Temperature +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating
AGENCY
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A