Emerson GXT5000R-208 Power Supply User Manual


 
24
SPECIFICATIONS
MODEL NUMBER GXT5000R-208
MODEL RATING VA/W 5000 / 3750
DIMENSIONS: inches (mm)
Unit: W x D x H 16.1 x 23.6 x 5.1(410 x 600 x 130)
Shipping: W x D x H 23.2 x 31.1 x 12.8 (590 x 790 x 325)
WEIGHT: lbs (kg)
Unit 41.2 (18.7)
Shipping 53.8 (24.4)
INPUT AC PARAMETERS
Voltage Range 208 VAC Nominal: 176-276 VAC
Frequency 50/60 Hz, ±5%; Auto Sensing
Input Power Cord 10 ft. attached, w/ NEMA L6-30P
OUTPUT AC PARAMETERS
Output Receptacles L6-30R (1), L6-20R (1)
Voltage 208 VAC, ±3%
Frequency 50 Hz or 60 Hz
Waveform Sinewave
Main Mode Overload 151 - 300% for 2 seconds;
126 - 150% for 10 seconds;
105 - 125% for 60 seconds with transfer to bypass
DC INPUT PARAMETERS
Voltage 240 VDC Nominal
Recharge Time 8 Hours to 90% capacity after full discharge into 100% load
ENVIRONMENTAL
Operating Temperature +32°F to +104°F (0°C to +40°C)
Storage Temperature +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
Audible Noise < 55 dBA
AGENCY
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A