Emerson MSM400 Computer Monitor User Manual


 
IP258
10
3.2 SPECIFICATIONS--MSM400
Housing ABS with polycarbonate lid, IP65
External dimensions 256.5 wide, 236.7 high, 95.0 deep, including wall mounting brackets
Cable Glands 3x 16mm holes and plastic glands supplied
3x 20mm holes and plastic glands supplied
Weight 2 kg
Wall Mounting holes 6 off Diam 5.0mm (See Drawing Section 4.5)
Power supply options 115 V a.c. (±15%) 50 / 60 Hz
230 V a.c. (±15%) 50 / 60 Hz
or 24 V d.c. (15 to 30 Volts)
Power consumption a.c. 10VA
d.c. 6W
Fuse (F1) 200 mA (T) 5 x 20mm
Current Output 0-20 or 4-20 mA selectable,
maximum load 1KΩ (at 22mA)
maximum applied voltage 48v d.c
HART HART digital communications, Two HART internal test terminals provided.
Relay Outputs 2x SPCO Relays, rated 5 Amps at 250 V a.c. Resistive
DC Power Output 24V DC for external sensors such as Mobrey Electrosensor
Sensor connections Terminals for Mobrey sensor Tx and Rx cables, each 2 cores and screen
Trigger inputs Unit accepts two 5V d.c.trigger input signals. 5V d.c. provided - compatible
with Mobrey Electrosensor
Terminals Max. cable size 2.5mm
2
Ambient temperature -30°C to 55°C
Max Altitude 2000m
Max Humidity 95% RH
Electrical Safety Conforms to EN61010-1
Installation Category Cat III 132V a.c. Max., Cat II 264V a.c. Max.
Pollution Degree 2
EMC Complies with EN61326 (Industrial level)