Emerson UPS Systems Power Supply User Manual


 
Battery Installation
13
Figure 10 Control cable layout—Liebert NXL UPS to Liebert NXL Battery Cabinet
The CAN cables must be two, twisted pair, shielded 18AWG (Belden 9156 or equivalent). All intercon-
necting cables and hardware for connected and attached cabinets will be provided.
NOTICE
Risk of improper installation. Can cause equipment damage.
During system commissioning, Liebert Services will set the jumpers on the EIB and the BIB.
If another battery cabinet is added to the system after commissioning, it is imperative that
Liebert Services reset the jumpers on the EIB board and the BIB board.