Falcon ED4000-A Power Supply User Manual


 
ED Series
TM
UVS PLUS
®
Model -A
ED Series Model -A Frequency Converter (120V Input/Output)
Model Number ED-1000-A ED-1500-A ED-2000-A ED-3000-A ED-4000-A
Nominal VA 1000 1500 2000 3000 4000
Electrical Input
AC Voltage, +10% -20% 120V 120V 120V 120V 120V
Current-Amps 10.4 15.6 20.8 29 39
Frequency Range 47 450 47 - 450 47 - 450 47 - 450 47 - 450
Electrical Output
AC Voltage,
±
3% 120V 120V 120V 120V 120V
Watts @ 50 or 60 Hz 700 1050 1400 2100 2800
Watts @ 400 Hz (-400 option) 595 892 1190 1785 2380
Current-Amps @ 50/60 Hz 8.3 12.5 16.7 25 33
Current-Amps @ 400Hz 7.1 10.6 14.2 21.3 28
50/60 Hz Non Linear
Repetitive Peak (Amps)
20 30 40 60 80
400 Hz Non Linear
Repetitive Peak (Amps)
14.2 21.3 28.3 42.5 56
Total Harmonic Distortion < 3% @ 100% Linear Load, < 5% @ 100% Non Linear Load
Overload 200% for 0.5 Seconds, 120% for 30 Seconds
Dynamic Response
±
5% RMS for 100% Step Load Change, 1ms Recovery Time
Output Protection Short Circuit and Overload
Electrical Connections
Input 6’ Cord with
5-15P
8’ Cord with
5-20P
8’ Cord with
L5-30P
Hardwired Hardwired
Output (4) 5-15R (4) 5-15R (4) 5-15R Hardwired Hardwired
Environmental
Operating Temperature 0º C to 35º C (32º F to 95º F)
Humidity 10% to 95% Non Condensing
Altitude 7,000 Feet
Cooling Low Velocity Forced Air Fans
Audible Noise @ 1.5 Meters 49dBA 54dBA
Controls and Indicators
Sequenced LEDs Load Level
Single LED Utility Present, Summary Alarm, Inverter On
Audible Alarms Utility Interrupt, Inverter Failure, Overload
Communications Dry Contact Closures on Utility Loss via 9 Pin “D” Connector
Mechanical
Dimensions H x W x D inches (mm) 13.5 x 6.25 x 19.4 (342.9 x 158.8 x 492.8)
Weight lb. (kg) 25 (11.3) 38 (17.2) 38 (17.2) 50 (22.7) 50 (22.7)
Specify input/output frequency, 50/60 or 400Hz (any combination).
Standard models shown. Custom configurations available; Consult Factory.
Note: For ED3000-A and ED4000-A models add a -400 to the end of the model number for a
400Hzoutput
14